SKU: X-400-I
Categories: Control by Web, IP Relays
Tags: ControlByWeb, Expansion BUS, Sensor, Temperature, X-400, X-600M
Web Enabled industrial logic Controller with BUS
- Expandable, Up to 64 I/O
- Relays, Analog & Digital Inputs
- Up to 16 temp sensors
- Description
- Features and Applications
- Specifications
- Downloads
Description
Flexible. Modular. Web-Enabled.
The ControlByWeb X-400 Bus Master Controller is a great drop-in solution for flexible data capture and use. The modular design boosts I/O options with a wide variety of compatible expansion modules. Peer-to-peer networking with other ControlByWeb devices on the network and it can extend the reach in physically challenging applications whether on the same network or via the cloud.
The X-400 Features
- Simple Web-Based Dashboard
- No-Code Logic Builder
- Peer-to-Peer Communication
- Ethernet I/O Monitoring & Control
- 400 Series Platform
The X-400 Applications
- Building Automation & Access Control
- Process Control
- Stadium Lighting Control
- Server Room Monitoring
- Remote/Field Monitoring & Control
- Dry Contact Monitoring/Notifications
- Security Camera Monitoring & Control
Power Requirements
- X-400-I
- Voltage:Ā 9-28 VDC
- Max Current:Ā (See Table)
Power Supply | Input Current (no expansion modules) | Input Current (X-400 + 1.7A for expansion modules) |
9 VDC | 134 mA | 1.834 A |
12 VDC | 101 mA | 1.801 A |
24 VDC | 55 mA | 1.755 A |
- X-400C-I-CA
- Voltage:Ā 9-28 VDC
- Max Current:Ā (See Table)
Power Supply | Input Current (no expansion modules) | Input Current (X-400C + 1.7A for expansion modules) |
9 VDC | 240 mA | 1.94 A |
12 VDC | 185 mA | 1.85 A |
24 VDC | 95 mA | 1.80 A |
Voltage Outputs
- Expansion Bus:Ā 1.7A max
Temperature Sensors
- Maximum Number of Sensors:Ā 16
- Type:Ā Dallas Semiconductor DS18B20
- Temperature Range:Ā -67Ā°F to 257Ā°F (-55Ā°C to +125Ā°C)
- Accuracy:Ā Ā±0.5Ā°C (from -10Ā°C to +85Ā°C)
- Sensor Functions:Ā Monitor Temperature, Log Temperature, Email Alerts, SNMP Traps
- Humidity Type:Ā ControlByWeb ModelĀ X-DTHS-PĀ sensor
- Humidity Range:Ā 0-100% RH
- Accuracy:Ā Ā±2%
- Max Cable Length:Ā 600 feet (180m) maximum combined cable length
Network
- Type:Ā 10/100 Base-T Ethernet Port
- Setup:Ā Static or DHCP IP address configuration
Connectors
- Power and 1-Wire Bus:Ā 5-Position, 3.81mm terminal spacing, Removable. For 16-28 AWG wire.
- Expansion Bus:Ā Ribbon cable, 10-conductor, polarized, 2Ć5-position, 0.100ā³ pitchĀ Provides power and communications for expansion modules (Communications: RS-485)
- Network:Ā 8-pin RJ-45
Real-Time Clock
- Manual or NTP(Network Time Protocol) setup
- NTP Sync Period:Ā Once, Daily, Weekly, On Powerup
- Auto Daylight Savings Adjustment
- Battery (capacitor) Power Backup
Capacitor Power Backup
- Backup Functions:Ā Retain Real-Time Clock, 1 Register, 2 Counters, 64 Relay States (local and expansion relays only)
- Backup Duration:Ā 2 week minimum
LED Indicators
- Number of LEDs:Ā 3
- Power on
- Network linked
- Network activity
Physical
- Operating Temperature:Ā -40Ā°F to 150Ā°F (-40Ā°C to 65.5Ā°C)
- Size:
- 1.41in (35.7mm) wide
- 3.88in (98.5mm) tall
- 3.1in (78mm) deep (not including connector)
- Weight:Ā 5 oz (142 grams)
- Enclosure Material:Ā Lexan 940 Polycarbonate Plastic
- Enclosure Flame Rating:Ā UL94 V0
Email Notifications
- Email Addresses:Ā 8
- Encrypted Email Alerts:Ā STARTTLS and TLS/SSL
- Alert Functions:Ā I/O states ā Fully customizable
Protocols
- HTTP, HTTPS, SSL, XML, Modbus TCP/IP, SNMP, SMTP, Remote Services
Logging
- Log File Size:Ā 3,072-Kbyte (up to 50,688 logs)
- Storage:Ā Nonvolatile Flash
- Buffer Architecture:Ā Circular Buffer
Log data can be periodically read and stored on a computer
Advanced Features
- Task Builder
- BASIC interpreter (up to 4-Kbytes script file size)
- Remote services
- ControlByWeb Cloud Compatible
Password Settings
- Password Length:Ā 6-18 Characters
Electromagnetic Compliance
- IEC CISPR 22, CISPR 24, EU EN55024, EN55022
- FCC 47CFR15 (Class B)
Product Safety Compliance
- IEC 61010-1
Download X-400 Datasheet. x-400