Web Enabled Dual Relay and Input Module 9-28Vdc/PoE
2 Relays & 2 Digital Inputs
Ethernet or WiFi Versions available
9-28VDC and/or POE
- Description
- Features and Applications
- Specifications
- Downloads
Description
Description
Simple, Powerful Ethernet I/O
The ControlByWeb X-401 with additional PoE power option, is easy to operate and a very capable Ethernet I/O PLC that’s an excellent fit for large and small IIoT applications. It can support up to 2 contacts and control up to 2 relays. You can configure and access your device simply through a standard web browser with no special software required.
Features and Applications
The X-401 Features
- Email Notifications
- No-Code Logic Builder
- Peer-to-Peer Communication
- Data Logging
- PoE and/or 9 – 28Vdc Powered
- WiFi Connectivity (X-401W Only)
The X-401 Applications
- Door & Access Control
- Network Device Rebooting
- Alarm Panel Monitoring
- Motor Control
Specifications
Power Requirements
- Voltage:
- X-401-I: 9-28 VDC
- X-401-E: POE and/or 9-28 VDC
- X-401W-I: 9-28 VDC
- X-401CW-I: 9-28 VDC
- Max Current: 233mA
Relay Contacts
- Number of Relays: 2
- Max Voltage: 28VAC, 24VDC
- Max Current: 3A
- Contact Type: SPDT (Form C)
- Load Type: General Purpose
- Contact Resistance: < 50 milliohms initial
- Contact Material: AgSnO2
- Electrical Life: 100K cycles (Typical)
- Mechanical Life: 10M cycles (Typical)
- Environmental Rating: Over voltage Category II, Pollution Degree 2
- Relay Modes: ON/OFF or Pulsed
- Pulse Timer Duration: 0.1 to 86,400 Seconds (1-day)
Digital Inputs
- Number of Inputs: 2
- Type: Optically-Isolated
- Voltage Range: 4-26VDC
- Current: 950uA @ 4V, 8.5mA @ 26V
- Minimum Hold Time: 20ms
- Input Functions: Monitor State, Control Relays, Control Remote Relays, Scalable Counter, On Timer, Total On Timer, Frequency
- Maximum Count: 24-bit
- Max Count Rate: 200Hz Max (Dependent on Configuration)
- Edge Trigger: Rising, Falling or Both
Real-Time Clock
- Manual or NTP(Network Time Protocol) setup
- NTP Sync Period: Once, Daily, Weekly, On Powerup
- Auto Daylight Savings Adjustment
- Battery (capacitor) Power Backup
Capacitor Power Backup
- Backup Functions: Retain Real-Time Clock, 1 Register, 2 Counters, 2 Relay States
- Backup Duration: 24 hours
Network
- Type: 10/100 Base-T Ethernet Port
- Setup: Static or DHCP IP address configuration
- Wireless: WiFi Communication (X-401W model only)
- Cellular Modem: WiFi Communication (X-401CW model only)
Connectors
- Power, Outputs, and Inputs: 14-Position, 3.81mm, Removable
- Network: 8-pin RJ-45
- Cell Antenna: Male SMA Connector (X-401CW model only)
LED Indicators
- Number of LEDs: 7
- Power on
- Relay coil energized 1-2
- Digital Inputs 1-2
- Network linked
- Network activity
Wireless
- Network Standards: IEEE 802.11 b/g/n
- Frequency Band: 2.412 – 2.462 GHz
- Wi-Fi Security Standards: WPA2, WPA3
- Network Settings: DHCP or Static
Physical
- Operating Temperature: -40°F to 150°F (-40°C to 65.5°C)
- Size:
- 1.41in (35.7mm) wide
- 3.88in (98.5mm) tall
- 3.1in (78mm) deep (not including connector)
- Weight: 5 oz (142 grams)
- Enclosure Material: Lexan 940 Polycarbonate Plastic
- Enclosure Flame Rating: UL94 V0
Protocols
- HTTP, HTTPS, SSL, XML, Modbus TCP/IP, SNMP, SMTP, Remote Services
Logging
- Log File Size: 3,072-Kbyte (up to 50,688 logs)
- Storage: Nonvolatile Flash
- Buffer Architecture: Circular Buffer
Log data can be periodically stored on a computer via FTP or email.
Advanced Features
- Task Builder
- BASIC interpreter
- Remote Services
Password Settings
- Password Length: 6-18 Characters
Electromagnetic Compliance
- IEC CISPR 22, CISPR 24
- EU EN55024, EN55022
- X-401-I: FCC 47CFR15 (Class B)
- X-401-E: FCC 47CFR15 (Class A)
Product Safety Compliance
- IEC 61010-1
Downloads