Expansion Module 6 Relays 6 Digital Inputs
The ControlByWeb X-20S™ expansion I/O module is used either with an X-400™ or X-600M™ controller. It has six high-current relays, each with Form-C contacts (SPDT), and six optically isolated digital inputs. Screw terminal strips provide connections to the relays.
- 6 Isolated HC Relays
- 6 Digital Inputs
Expansion Module for the X-400 and X-600M
- Description
- Features and Applications
- Specifications
Description
Limit Switches, Motors, Valves, & More
The X-20S has been designed for use with controlling relatively heavy loads such as motors, solenoid valves, and lights etc.. Note: That switches can be connected to the X-20S digital inputs to enable local control of these loads. The digital inputs can also be used for other monitoring applications such as limit switches, security sensors, or light switches.
X-20S Features
- 6 isolated relays SPDT (Form C)
- Relay functions: On, Off, Pulse
- Thermoplastic, UL94V-0, 3-wall, 0.375 inch pitch
- 6 optically isolated digital inputs
- Digital input functions:
- Monitor State
- Control Relays
- Control Remote Relays
- Count
- Frequency
- High Time
- ON Time
- 13 LEDs for outputs, inputs, and power
- Power Supply: 9-28 VDC (24V recommended)
Power Requirements
- Voltage:Â 9-28 VDC (24V recommended)*
- Max Current: See table below for typical values at 25°C.
Power Supply | All Relays OFF | All Relays ON |
9 VDC | 20 mA | 750 mA |
12 VDC | 16 mA | 555 mA |
24 VDC | 12 mA | 285 mA |
Relay Contacts
- Number of Relays:Â 6
- Max Voltage:Â 277VAC, 30VDC
- Max Current:Â 15A
- Contact Type:Â SPDT (Form C)
- Load Type:Â General Purpose
- Contact Resistance:Â < 30 milliohms initial
- Contact Material:Â AgSnO2
- Electrical Life:Â 100K cycles (Typical)
- Mechanical Life:Â 10M cycles (Typical)
- Environmental Rating:Â Over voltage Category II, Pollution Degree 2
- Relay Modes:Â ON/OFF or Pulse
- Pulse Timer Duration:Â 0.1 to 86,400 Seconds (1-day)
Digital Inputs
- Number of Inputs:Â 6
- Type:Â Optically-Isolated
- Voltage Range:Â 4-28VDC
- Vin Hi (Min):
- Vin LO (Max):
- Current:Â 950uA @ 4V, 8.5mA @ 26V
- Minimum Hold Time:
- Input Isolation:Â 1500V
- Input Functions:Â Asynchronous status of the digital inputs
- Number of Counter Inputs:Â 6
- Maximum Count:Â 32-bit
- Max Count Rate:Â 200 Hz
- Edge Trigger:Â Rising, Falling or Both
- Frequency:Â 1 Hz min, 200 Hz max
- High Time:Â Pulse width (4,194,304 seconds max)
- On Time:Â Accumulated time an input is asserted (4,194,304 seconds max)
Connectors
- Expansion Connector: Ribbon cable, 2×5-position, polarized 0.100″ pitch
- Relays: Thermoplastic, UL94V-0, 3-wall, 0.375″ pitch
- Inputs:Â PCB terminal block, screw connection, 3.81mm pitch
LED Indicators
- Number of LEDs:Â 13
- Power on
- Relays 1-6
- Digital Inputs 1-6
Physical
- Size:
- 8.60in (218.44mm) wide
- 4.95in (125.73mm) tall
- 2.16in (54.86mm) deep
- Weight:Â 17 oz (474 g)
- Enclosure Material:Â PVC
- Enclosure Flame Rating:Â UL94 V1
Environmental
- Operating Temperature: -40°F to 135°F (-40°C to 57°C)
- Storage Temperature: -40°F to 185°F (-40°C to 85°C)
- Humidity:Â 5-95%, non-condensing
- Altitude:Â Up to 2,000m
- Indoor use or NEMA-4 protected location
Electromagnetic Compliance
- IEC CISPR 22, CISPR 24
- FCC 47CFR15 (Class B)
- EN55024 ITE Immunity (2010)
- EN55022 Emissions (2010)
Product Safety Compliance
- UL 61010-1 (Electrical Equipment for Measurement, Control, and Laboratory Use)