Expansion Module 6 Relays 6 Digital Inputs
The ControlByWeb X-20Sā¢ expansion I/O module is used either with an X-400ā¢ or X-600Mā¢ controller. It has six high-current relays, each with Form-C contacts (SPDT), and six optically isolated digital inputs. Screw terminal strips provide connections to the relays.
- 6 Isolated HC Relays
- 6 Digital Inputs
Expansion Module for the X-400 and X-600M
- Description
- Features and Applications
- Specifications
Description
Limit Switches, Motors, Valves, & More
The X-20S has been designed for use with controlling relatively heavy loads such as motors, solenoid valves, and lights etc.. Note: That switches can be connected to the X-20S digital inputs to enable local control of these loads. The digital inputs can also be used for other monitoring applications such as limit switches, security sensors, or light switches.
X-20S Features
- 6 isolated relays SPDT (Form C)
- Relay functions: On, Off, Pulse
- Thermoplastic, UL94V-0, 3-wall, 0.375 inch pitch
- 6 optically isolated digital inputs
- Digital input functions:
- Monitor State
- Control Relays
- Control Remote Relays
- Count
- Frequency
- High Time
- ON Time
- 13 LEDs for outputs, inputs, and power
- Power Supply: 9-28 VDC (24V recommended)
Power Requirements
- Voltage:Ā 9-28 VDC (24V recommended)*
- Max Current:Ā See table below for typical values at 25Ā°C.
Power Supply | All Relays OFF | All Relays ON |
9 VDC | 20 mA | 750 mA |
12 VDC | 16 mA | 555 mA |
24 VDC | 12 mA | 285 mA |
Relay Contacts
- Number of Relays:Ā 6
- Max Voltage:Ā 277VAC, 30VDC
- Max Current:Ā 15A
- Contact Type:Ā SPDT (Form C)
- Load Type:Ā General Purpose
- Contact Resistance:Ā < 30 milliohms initial
- Contact Material:Ā AgSnO2
- Electrical Life:Ā 100K cycles (Typical)
- Mechanical Life:Ā 10M cycles (Typical)
- Environmental Rating:Ā Over voltage Category II, Pollution Degree 2
- Relay Modes:Ā ON/OFF or Pulse
- Pulse Timer Duration:Ā 0.1 to 86,400 Seconds (1-day)
Digital Inputs
- Number of Inputs:Ā 6
- Type:Ā Optically-Isolated
- Voltage Range:Ā 4-28VDC
- Vin Hi (Min):
- Vin LO (Max):
- Current:Ā 950uA @ 4V, 8.5mA @ 26V
- Minimum Hold Time:
- Input Isolation:Ā 1500V
- Input Functions:Ā Asynchronous status of the digital inputs
- Number of Counter Inputs:Ā 6
- Maximum Count:Ā 32-bit
- Max Count Rate:Ā 200 Hz
- Edge Trigger:Ā Rising, Falling or Both
- Frequency:Ā 1 Hz min, 200 Hz max
- High Time:Ā Pulse width (4,194,304 seconds max)
- On Time:Ā Accumulated time an input is asserted (4,194,304 seconds max)
Connectors
- Expansion Connector:Ā Ribbon cable, 2Ć5-position, polarized 0.100ā³ pitch
- Relays:Ā Thermoplastic, UL94V-0, 3-wall, 0.375ā³ pitch
- Inputs:Ā PCB terminal block, screw connection, 3.81mm pitch
LED Indicators
- Number of LEDs:Ā 13
- Power on
- Relays 1-6
- Digital Inputs 1-6
Physical
- Size:
- 8.60in (218.44mm) wide
- 4.95in (125.73mm) tall
- 2.16in (54.86mm) deep
- Weight:Ā 17 oz (474 g)
- Enclosure Material:Ā PVC
- Enclosure Flame Rating:Ā UL94 V1
Environmental
- Operating Temperature:Ā -40Ā°F to 135Ā°F (-40Ā°C to 57Ā°C)
- Storage Temperature:Ā -40Ā°F to 185Ā°F (-40Ā°C to 85Ā°C)
- Humidity:Ā 5-95%, non-condensing
- Altitude:Ā Up to 2,000m
- Indoor use or NEMA-4 protected location
Electromagnetic Compliance
- IEC CISPR 22, CISPR 24
- FCC 47CFR15 (Class B)
- EN55024 ITE Immunity (2010)
- EN55022 Emissions (2010)
Product Safety Compliance
- UL 61010-1 (Electrical Equipment for Measurement, Control, and Laboratory Use)